OS GSO IEC 62146-2:2024

IEC 62146-2:2023
Omani Standard   Current Edition · Approved on 14 October 2024

Capacitors for high‑voltage alternating current circuit‑breakers - Part 2: TRV capacitors

OS GSO IEC 62146-2:2024 Files

OS GSO IEC 62146-2:2024 Scope

IEC 62146-2:2023 is applicable to TRV capacitors used on high-voltage alternating current circuit-breakers with rated voltages above 100 kV with 50 Hz or 60 Hz.
TRV capacitors are installed phase to earth, either in parallel to the bushing on dead tank circuit-breakers, or immersed inside the circuit-breaker, or freestanding close to the circuit-breaker. Their function is to limit the transient recovery voltage (TRV) and the rate of rise of recovery voltage (RRRV) on the circuit-breaker. Capacitors in compliance with this document can be used as TRV capacitor.
This document applies to TRV capacitors falling into one or both of the following categories for:
- mounting on or close to air insulated switchgear (AIS) dead tank and live tank circuit-breakers, or
- mounting on gas insulated switchgear (GIS) circuit-breakers.
The testing for each of the above applications is in some cases different.
This document does not apply to grading capacitors installed in parallel to the chambers of the circuit-breaker, which are specified in IEC 62146-1.
This document does not apply to capacitors not directly associated with high-voltage alternating current circuit-breakers.
The object of this document is:
- to define uniform rules regarding performances, testing and rating
- to define specific safety rules
- to provide a guidance for installation and operation
The TRV capacitor is a sub-component for the circuit-breaker and is specified in accordance with the circuit-breaker specifications according to IEC 62271-1, IEC 62271-100, and if applicable to IEC 62271-203.
TRV capacitors are commonly built with composite or ceramic housings (insulators). Those insulators follow IEC 61462 or IEC 62155. Other housings can be used if they can sustain applicable type tests according to IEC 61462 and IEC 62155.
This International Standard is to be used in conjunction with IEC 62146-1:2013 and IEC 62146-1:2013/AMD1:2016.

Best Sellers From Electrical Sector

GSO 2530:2016
 
Gulf Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
OS GSO 2530:2016
GSO 2530:2016 
Omani Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
OS GSO 34:2007
GSO 34:2007 
Omani Standard
LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES
GSO 34:2007
 
Gulf Technical Regulation
LEAD-ACID STARTER BATTERIES USED FOR MOTOR VEHICLES AND INTERNAL COMBUSTION ENGINES

Recently Published from Electrical Sector

OS GSO IEC 60034-12:2025
IEC 60034-12:2024 
Omani Standard
Rotating electrical machines - Part 12: Starting performance of single-speed three-phase cage induction motors
OS GSO IEC TR 63401-4:2025
IEC TR 63401-4:2022 
Omani Standard
Dynamic characteristics of inverter-based resources in bulk power systems - Part 4: Behaviour of inverter-based resources in response to bulk grid faults
OS GSO IEC TS 61400-26-4:2025
IEC TS 61400-26-4:2024 
Omani Standard
Wind energy generation systems - Part 26-4: Reliability for wind energy generation systems
OS GSO IEC 61347-2-11:2025
IEC 61347-2-11:2024 
Omani Standard
Controlgear for electric light sources - Safety - Part 2-11: Particular requirements - Miscellaneous electronic circuits used with luminaires